1
AIR CONDITIONING
06.04 Ref. 88320A (En) Rev. 100
VERTICAL SELF CONTAINED WATER TO AIR HEAT PUMPS
WCVBZ SERIES
COOLING CAPACITIES
ENTER
AIR WET
BULB
EVAP. AIR FLOW
l/s
TEMP.
CONDENSING TEMPER ºC
35
40
45
50
35
40
45
50
35
40
45
50
TOTAL CAPACITY
kW
5,35
5,13
4,89
4,65
7,22
6,93
6,61
6,27
9,81
9,41
8,97
8,52
POWER INPUT
kW
1,62
1,77
1,93
2,10
2,23
2,45
2,67
2,90
2,98
3,26
3,55
3,87
SENSIBLE
EDBT
19 ºC
3,83
3,68
3,54
3,39
5,17
4,97
4,78
4,58
7,02
6,75
6,49
6,22
15
COOLING
21ºC
4,40
4,24
4,09
3,95
5,93
5,72
5,53
5,33
8,06
7,77
7,51
7,24
kW
23ºC
4,96
4,81
4,66
4,52
6,69
6,49
6,30
6,10
9,09
8,82
8,55
8,29
25ºC
5,35
5,13
4,89
4,65
7,22
6,93
6,61
6,27
9,81
9,41
8,97
8,52
TOTAL CAPACITY
kW
5,79
5,57
5,33
5,08
7,82
7,52
7,20
6,86
10,61
10,21
9,77
9,32
POWER INPUT
kW
1,65
1,81
1,97
2,14
2,28
2,50
2,72
2,95
3,04
3,33
3,62
3,93
SENSIBLE
EDBT
21ºC
3,83
3,68
3,53
3,38
5,16
4,96
4,76
4,57
7,01
6,74
6,46
6,20
17
COOLING
23ºC
4,39
4,24
4,09
3,95
5,93
5,72
5,52
5,33
8,05
7,77
7,50
7,24
kW
25ºC
4,95
4,80
4,65
4,51
6,68
6,48
6,28
6,09
9,08
8,80
8,53
8,27
27ºC
5,52
5,37
5,22
5,08
7,45
7,25
7,04
6,86
10,12
9,84
9,56
9,31
TOTAL CAPACITY
kW
6,22
6,00
5,77
5,52
8,40
8,10
7,79
7,45
11,40
11,00
10,57
10,12
POWER INPUT
kW
1,70
1,85
2,01
2,18
2,35
2,55
2,77
3,00
3,13
3,40
3,69
4,00
SENSIBLE
EDBT
23ºC
3,82
3,67
3,52
3,38
5,16
4,96
4,76
4,57
7,01
6,74
6,46
6,20
19
COOLING
25ºC
4,38
4,24
4,09
3,95
5,92
5,72
5,52
5,33
8,03
7,77
7,50
7,24
kW
27ºC
4,95
4,80
4,65
4,51
6,68
6,48
6,28
6,09
9,07
8,80
8,53
8,27
29ºC
5,52
5,37
5,22
5,08
7,45
7,25
7,05
6,86
10,12
9,84
9,57
9,31
TOTAL CAPACITY
kW
6,66
6,44
6,21
5,95
8,99
8,69
8,38
8,03
12,21
11,80
11,38
10,90
POWER INPUT
kW
1,74
1,89
2,04
2,21
2,40
2,60
2,81
3,05
3,21
3,47
3,75
4,07
SENSIBLE
EDBT
25ºC
3,79
3,65
3,50
3,36
5,12
4,92
4,73
4,54
6,95
6,69
6,42
6,16
21
COOLING
27ºC
4,38
4,23
4,08
3,94
5,91
5,71
5,51
5,32
8,02
7,75
7,48
7,22
kW
29ºC
4,94
4,79
4,64
4,50
6,66
6,47
6,26
6,07
9,05
8,78
8,51
8,25
31ºC
5,51
5,36
5,21
5,07
7,44
7,24
7,03
6,84
10,10
9,83
9,55
9,29
UK CONDITIONS 22 ºC DB - 16ºC WB
TOTAL
5,35
5,69
4,87
TOTAL
7,23
7,69
6,57
TOTAL
9,81
10,43
8,92
40ºC COND - 47ºC COND - 50ºC COND
SENS
4,24
4,45
3,95
SENS
5,72
6,00
5,33
SENS
7,78
8,15
7,24
IMPUT
1,79
1,56
2,12
IMPUT
2,48
2,16
2,93
IMPUT
3,30
2,87
3,90
WCVBZ351
639
UNIT SIZE
555
WCVBZ201
WCVBZ251
417
Notes
1. Cooling capacities are NET after deduction of indoor standard motor heat
4. When Evaporator Coil air flow is different from the nominal air flow use following multipliers:
MODEL
MULTIPLIER
PERCENT OF AIR FLOW
80%
90%
100%
110%
120%
K
T
0,95
0,97
1
1,03
1,05
KT= Total Capacity
ALL MODELS
KS
0,92
0,96
1
1,04
1,08
Ks= Sensible Capacity
KW
0,96
0,98
1
1,02
1,03
Kw = Power Input
2 EDBT- Entering Air Dry Bulb Temp. (ºC)
3. Power Imput (kW): Total Unit Power Imput.
ENTER
AIR WET
BULB
EVAP. AIR FLOW
l/s
TEMP.
CONDENSING TEMPER ºC
35
40
45
50
TOTAL CAPACITY
kW
11,60
11,12
10,60
10,07
POWER INPUT
kW
3,46
3,79
4,13
4,49
SENSIBLE
EDBT
19 ºC
8,30
7,98
7,67
7,35
15
COOLING
21ºC
9,52
9,18
8,87
8,55
kW
23ºC
10,74
10,42
10,11
9,80
25ºC
11,60
11,12
10,60
10,07
TOTAL CAPACITY
kW
12,54
12,07
11,55
11,02
POWER INPUT
kW
3,53
3,87
4,21
4,57
SENSIBLE
EDBT
21ºC
8,29
7,96
7,64
7,33
17
COOLING
23ºC
9,51
9,19
8,86
8,55
kW
25ºC
10,73
10,40
10,08
9,78
27ºC
11,96
11,63
11,30
11,00
TOTAL CAPACITY
kW
13,47
13,00
12,50
11,96
POWER INPUT
kW
3,64
3,95
4,29
4,65
SENSIBLE
EDBT
23ºC
8,28
7,96
7,64
7,33
19
COOLING
25ºC
9,50
9,18
8,86
8,55
kW
27ºC
10,72
10,40
10,08
9,77
29ºC
11,95
11,63
11,31
11,00
TOTAL CAPACITY
kW
14,43
13,95
13,45
12,88
POWER INPUT
kW
3,72
4,03
4,36
4,72
SENSIBLE
EDBT
25ºC
8,22
7,90
7,59
7,28
21
COOLING
27ºC
9,48
9,16
8,84
8,53
kW
29ºC
10,69
10,38
10,05
9,75
31ºC
11,93
11,61
11,29
10,98
UK CONDITIONS 22 ºC DB - 16ºC WB
TOTAL
11,60
12,33
10,55
40ºC COND - 47ºC COND - 50ºC COND
SENS
9,19
9,63
8,56
IMPUT
3,83
3,34
4,53
UNIT SIZE
WCVBZ401
666
Hushon UK